A refrigerant is a compound used in a heat cycle that undergoes a phase change from a gas to a liquid and back. The two main uses of refrigerants are refrigerators/freezers and air conditioners. Cf. coolant.

The ideal refrigerant has good thermodynamic properties, is noncorrosive, and safe. The desired thermodynamic properties are a boiling point somewhat below the target temperature, a high heat of vaporization, a moderate density in liquid form, and a relatively high density in gaseous form. Since boiling point and gas density are affected by pressure, refrigerants may be made more suitable for a particular application by choice of operating pressure.

Corrosion properties are a matter of materials compatibility with the components used for the compressor, piping, evaporator, and condenser. Safety considerations include toxicity and flammability.

Early mechanical refrigeration systems employed sulfur dioxide gas or anhydrous ammonia, with small home refrigerators primarily using the former. Being toxic, sulfur dioxide rapidly disappeared from the market with the introduction of Freon. Ammonia is still used in some large commercial plants, well away from residential areas, where a leak will not cause widespread injuries.

Until concerns about depletion of the ozone layer arose in the 1980s, the most widely used refrigerants were the halomethanes R-12 and R-22, with R-12 being more common in automotive air conditioning and small refrigerators, and R-22 being used for residential and light commercial air conditioning, refrigerators, and freezers. Some very early systems used R-11 because its low boiling point allows low-pressure systems to be constructed, reducing the mechanical strength required for components. New production of R-12 ceased in the United States in 1995, and R-22 is to be phased out in 2010. R-134a and certain blends are now replacing chlorinated compounds. One popular 50/50 blend of R-32 and R-125 now being increasingly substituted for R-22 is marketed under the trade name Puron®.

Use of highly purified liquified propane gas as a refrigerant is gaining favor, especially in systems designed for R-12, R-22 or R-134a. As such, it is designated as R-290 and is marketed under the trade name Duracool®. Although propane is flammable, in home and automotive systems it is present in quantities small enough to not pose an undue fire hazard if a system should develop a leak. Moreover, propane is nontoxic. An odorant, such as methyl mercaptan, can be added in trace amounts to alert persons of system leaks.

Numbering

The R-# numbering system was developed by DuPont and systematically identifies the molecular structure of refrigerants made with a single halogenated hydrocarbon. The meaning of the codes is as follows:

For example, R-134a has 4 fluorine atoms, 2 hydrogen atoms, 2 carbon atoms, with an empirical formula of tetrafluoroethane. The "a" suffix indicates that the isomer is unbalanced by one atom, giving 1,1,1,2-Tetrafluoroethane. R-134 without the "a" suffix would have a molecular structure of 1,1,2,2-Tetrafluoroethane — a compound not especially effective as a refrigerant.

The same numbers are used with an R- prefix for generic refrigerants, with a "Propellant" prefix (e.g., "Propellant 12") for the same chemical used as a propellant for an aerosol spray, and with trade names for the compounds, such as "Freon 12." Recently, a practice of using HFC- for hydrofluorocarbons, CFC- for chlorofluorocarbons, and HCFC- for hydrochlorofluorocarbons has arisen, due to the regulatory differences among these groups.